Rigid Diaphragm Method
The total lateral load is distributed between the shear walls based on the relative capacities.
Figure E3 is a graphical representation of the mechanical model based on a continuous rigid
beam approach. For the first iteration, the segmented shear wall method is used to determine the
wall capacities. Table E3 summarizes individual shear wall loads.
Figure E3
Rigid Diaphragm Method Model
TABLE E3
SHEAR WALL LOADS ACCORDING TO RIGID DIAPHRAGM METHOD
Shear Wall #
Segmented Shear Wall
Length, ft
Fraction of Total Wall
Length
Shear Wall Load, lb
Wall 1 29.0 0.42 8,400
Wall 2 9.0 0.13 2,600
Wall 3 15 0.22 4,400
Wall 4 16 0.23 4,600
TOTAL 69.0 1.0 20,000
Table E4 compares results of flexible vs. rigid diaphragm methods. The flexible diaphragm
method both underestimates and overestimates the shear wall loads as compared to the rigid
diaphragm method. While providing a more conservative design, the flexible diaphragm method
requires an impractical shear wall schedule for this building configuration (Figure E1). For
example, Wall 2 has to be excluded from the analysis, because it is impractical to design a short
wall segment that accounts for only 13 percent of the total shear wall length of the building in the
North-South direction to resist as much as 41 percent of the total story shear load. Although
Walls 3 and 4 have practically the same lengths, according to the flexible diaphragm method,
Wall 3 should have capacity four times greater than that of Wall 4. The differences between the
two methods diminish in significance for simple rectangular buildings that resist shear loads by
only two exterior walls. Appendix C discusses the methods of lateral load distribution and
examines aspects and limitations of various methods of analysis.
E-3