COMPLIANCE SCHEDULE HANDBOOK Compliance schedule content guidelines
25 May 2007
DEPARTMENT OF BUILDING AND HOUSING
14
Some signs may be covered by the two
specified systems, for example, a sign
indicating how to use a manual call point. It is
suggested that where this occurs, a practical
approach is to categorise the sign based on the
primary reason for which it was installed. In the
case of manual call points, SS 14 would be the
most appropriate as the sign has been installed
as part of an SS 2 (emergency warning systems)
item. An exit sign leading to an automatic door
would be listed under SS 15 as the sign is
there for escape purposes, not to provide
instructions to the user on how to operate
the automatic door.
Signs are listed under two separate specified
systems in the Regulations. This arrangement
in the Regulations does not mean that there
is a requirement that the specified systems be
listed in any particular way on a compliance
schedule. For instance, each primary specified
system (SS 1–13) could be listed on a
compliance schedule and where appropriate
have SS 14 signs as a subcategory describing
the signs that relate to them and their inspection,
maintenance and reporting procedures. The
same could be done for emergency power
systems.
3.0 System description
It is essential that a compliance schedule is
specifically tailored to a building and its
specified system(s). This is important to ensure
the ongoing performance of the specified
systems to the required performance standards
and to allow those carrying out and auditing
the compliance schedule requirements to
understand what is required.
As a minimum, a basic description of the
system, its purpose, location and extent of
installation should be provided on the
compliance schedule to assist those carrying
out the inspection and maintenance procedures.
It can be helpful to include the relevant building
consent documentation or drawings and
specifications on the compliance schedule.
This information will assist users to understand
the system design, installation and operation.
Example:
SS 7
7.1: 15 mm double check valve assembly –
boiler feed supply – located in the level 9
plantroom – see building consent BC5394,
drawing 4 page 5 (attached)
7.2: 20 mm double check valve assembly –
swimming pool make up water supply – located
on level 2 – see building consent BC5394,
drawing 2 page 5 (attached)
Assigning a reference number to each specified
system will help to distinguish between different
specified systems of the same type. These
reference numbers can then be used on plans to
help identify a specified system’s location.
3.1 Guideline provisions
Although Part 2 of the Compliance schedule
content guidelines provides a general scope
and some examples for each specified system,
it does not provide a system description,
as these are specific to each system and its
arrangement within a building.
4.0 Inspection and maintenance
The Building Act requires that each specified
system have inspection and maintenance
procedures to ensure the system is performing,
and continues to perform, to the performance
standards set out for that specified system.
The inspection, maintenance, and reporting
procedures need to be relevant to the
performance standard, and therefore the way
the system was designed, to ensure the
specified system continues to perform in the
way it was intended.
Often a New Zealand or international Standard
will be suitable for the inspection and
maintenance procedures for a particular
specified system. In other cases it may be an
inspection and maintenance document provided
by the manufacturer/designer of the system,
or it may be an inspection document prepared
by a person qualified to do so (this may be
developed using a combination of