16
Commander SE
www.emersonct.com
Commander SE
Simple and Easy
Overview
Control Techniques’ economical microdrive is an AC
open loop vector powerhouse, combining unmatched
flexibility with a small footprint. Best of all, the
Commander SE is simple to use and easy to install.
The Commander SE’s first 10 parameters meet the
needs of 80% of drive applications, making setup fast
and effortless. Installation requires only a standard
screwdriver, while the removable control terminal strip
makes changeover quick and error free.
The rugged and robust design has been field tested
in harsh environments and proven itself a dependable
drive for a wide range of applications. The Commander
SE, with its Intelligent Thermal Management (ITM)
technology, was designed with reliability in mind. Rated
at 50°C ambient temperature, the Commander SE
withstands the most severe operating conditions.
Digital AC Drive
1/3 to 3 HP, 1 phase, 230 VAC
1 to 10 HP, 3 phase, 230 VAC
1 to 50 HP, 3 phase, 460 VAC
NEMA 1 (IP21) enclosure
RS485 serial communications with
Modbus RTU protocol
Plug-in communications via Profibus-DP,
DeviceNet, and Interbus-S
SESoft Windows based
configuration tool
QuicKey cloning module
Ideal for pumps, conveyors, mixers, fans,
ovens and more
Advanced menus for ultimate control and
flexibility
Complete Motor Solutions
A
P
P
R
O
V
A
L
I
S
O
9
0
0
2
—Mixer
—Simple and Easy
—Material Payoff
—Performance
Commander SE
17
1-800-893-2321
Feature
Performance Advantage
Open loop vector control with true space vector
modulation
Precise control algorithm provides full torque down to
1 Hz for exceptional performance
Access to multiple parameter levels
Customizes the drive to meet each user’s needs: simple
(level 1), flexible (level 2) and advanced (level 3)
QuicKey cloning module
Provides fast and cost-effective drive-to-drive parameter
transfer and storage with no PC required
Terminal connection drawings and Level 1 parameters (10)
listed on the drive’s front cover
On-the-spot easy reference for drive set-up and maintenance
Static auto-tune
Allows fast motor / drive optimization without motor shaft
rotation
Two sets of motor map parameters saved in the drive’s memory
Allows sequenced switching between two motors with
different operating characteristics
Configurable analog and digital I/O
Customizes drive to the specific application
S-ramp accel / decel profiling
Provides smooth speed transitions, minimizing machine
“jerk”
Built-in independent PID control
Eliminates the need for an external PID controller while
providing “outer loop” control of a process variable
Built-in MOP (motorized potentiometer)
Emulates the functionality of the traditional MOP with
increase / decrease pushbuttons
8 Preset speeds with independent accel / decel ramps
Allows predetermined speed sequencing via logic inputs
Selectable Stopping modes including Ramp, Coast, DC
Injection, and Dynamic Braking (except size 1)
Added flexibility meets many application requirements
Full EMC compliance with optional filter
Meets global standards for worldwide use
0.33 1 1.5 2.25 1 SE11200025
0.50 1 2.3 3.45 1 SE11200037
0.75 1 3.1 4.65 1 SE11200055
1 1 4.3 6.45 1 SE11200075
1 1 or 3 4.3 6.45 2 SE2D200075
2 1 or 3 7.5 11.3 2 SE2D200150
3 1 or 3 10 15 2 SE2D200220
5 3 17 25 2 SE23200400
7.5 3 25 37.5 3 SE33200550
10 3 28.5 42.8 3 SE33200750
Motor HP
208 / 230 VAC
Order String
SizeContin.
Output
Current
(A)
Overload
Current
(A)
Input
Phase
Catalog
Number
1 3 2.1 3.15 2 SE23400075
2 3 4.2 6.3 2 SE23400150
3 3 5.8 8.7 2 SE23400220
5 3 9.5 14.3 2 SE23400400
7.5 3 13 19.5 3 SE33400550
10 3 16.5 24.8 3 SE33400750
15 3 24.5 36.8 4 SE43401100
20 3 30.5 45.8 4 SE43401500
25 3 37 55.5 4 SE43401850
30 3 46 69.0 5 SE53402200
40 3 60 90.0 5 SE53403000
50 3 70 105.0 5 SE53403700
Motor HP
380 / 480 VAC
SizeContin.
Output
Current
(A)
Overload
Current
(A)
Input
Phase
Catalog
Number
Ratings: Commander SE
SINGLE OR THREE PHASE INPUT
.33 to 10 HP (208-230 VAC)
1 to 50 HP (380-460 VAC)
Motor HP is based on four pole, 230 / 460 VAC NEMA ratings.
Overload: 150% for one minute.
SE X X X X X X X X
Drive Kilowatt Rating
Place Holder (0)
Drive Voltage Rating: 2 = 208-230 VAC
4 = 380-460 VAC
Input Phase: 1 = 1, D = 1 & 3, 3 = 3
Size: 1, 2, 3, 4, 5
Commander SE Product Family
18
Commander SE
www.emersonct.com
Terminal Diagram: Commander SE
Terminal Description
Pin
#
Function Type/Description Notes
1 0V Common Common for
External
Analog Signals
2 Analog Input 1 Single-ended 0 to +10 VDC,
(Local Frequency / Analog Input 100k Ohms,
Speed Reference), 10 bit Sample Time 6ms
3 +10 VDC User Supply Reference Supply 5 mA max
Short Circuit
Protected
4 0V Common Common for
External
Digital Signals
5 Analog Input 2 Single-ended 4-20 mA
input,
(Remote Frequency / Analog Input 200 Ohms,
Speed Reference), 10 bit Sample Time 6ms
6 Analog Output 1 Single-ended 0 to +10 VDC
(Frequency / Speed), 10 bit Analog Output, @ 5 mA max
Unipolar Update Time 22ms
7 +24 VDC User Supply User Supply 100 mA max
Short Circuit Protected
8 Digital I/O 1 Digital 0 to 24 VDC,
(Zero Speed Output) Input / Output 7.5k Ohms input or
0 to 24 VDC,
50 mA max output
Update Time 1.5ms
Pin
#
Function Type/Description Notes
9 Digital Input Digital Input 0 to 24 VDC,
(Enable) 7.5k Ohms
Update Time 1.5ms
10 Digital Input Digital Input 0 to 24 VDC,
(Run Forward) 7.5k Ohms
Update Time 1.5ms
11 Digital Input Digital Input 0 to 24 VDC,
(Run Reverse) 7.5k Ohms
Update Time 1.5ms
12 Digital Input Digital Input 0 to 24 VDC,
(Local/Remote Select) 7.5k Ohms
Update Time 1.5ms
13 Digital Input Digital Input 0 to 24 VDC,
(Jog Select) 7.5k Ohms
Update Time 1.5ms
14 +24 VDC User Supply User Supply 100 mA max
Short Circuit Protected
15 Status Relay (Drive Healthy) Normally Open 240 VAC, 6A resistive
16 Status Relay (Drive Healthy) Normally Open 240 VAC, 6A resistive
Values in parenthesis designate default functions.
0-20, 20-0, and 20-4 mA are also available. See Commander SE Manual.
Programmable Analog Programmable Digital All Analog I/O is scaleable
Commander SE
19
1-800-893-2321
Specifications: Commander SE
Environment
Ambient Operating -10ºC to 40ºC (14ºF to 104ºF) @ 6kHz carrier freq.
Temperature -10ºC to 50ºC (14ºF to 122ºF) @ 3kHz carrier freq.
For SE Size 4—25HP and all SE Size 5's.
-10ºC to 40ºC (14ºF to 104ºF) @ 3kHz carrier freq.
Cooling method Convection and forced convection,
model dependent
Humidity 95% maximum non-condensing at 40ºC (104ºF)
Storage Temperature -40ºC to 60ºC (-40ºF to 140ºF) -- 12 months Max.
Altitude Derate the continuous output current by
1% for every 100m (328 ft) above 1000m (3280
ft) to a maximum of 4000m (13,000 ft).
Vibration Tested in accordance with IEC 68-2-34
and IEC 68-2-36
Mechanical Shock Tested in accordance with IEC 68-2-29
Enclosure NEMA 1 (IP 21)
Electromagnetic In compliance with EN61800-3 and EN50082-2
Immunity
Electromagnetic In compliance with EN61800-3
Emissions second environment, without RFI filter.
EN50081-1*, EN500821-2 and EN50081-3 first
environment with optional RFI filter. *Size 1 only
AC Supply Requirements
Voltage 200V model: 200 to 240 VAC ±10%
400V model: 380 to 480 VAC ±10%
Phase 1Ø and (Model Dependent)
Maximum Supply 2% negative phase sequence (3% voltage
Imbalance imbalance between phases)
Frequency 48 to 62 Hz
Input Displacement 0.97
Power Factor
Control
Carrier Frequency 3, 6 and 12 kHz (Default Value Model Dependent
)
Output Frequency Up to 1000 Hz
Frequency Accuracy ±0.01% of full scale
Frequency Resolution 0.1 Hz
Analog Input 10 Bit + sign (Qty 2)
Resolution
Serial Communications ANSI 2-wire EIA485 via RJ45 connector.
Baud rate is 4800, 9600 or 19,200
Braking DC injection braking standard. Dynamic braking
transistor standard (not available on Size 1).
Protection
DC Bus 200V model: 180 VDC
Undervoltage Trip (approximately 127 VAC line voltage)
400V model: 400 VDC
(approximately 282 VAC line voltage)
DC Bus 200V model: 420 VDC
Overvoltage Trip (approximately 299 VAC line voltage)
400V model: 830 VDC
(approximately 587 VAC line voltage)
MOV Voltage 160 Joules, 1400 VDC clamping
Transient Protection (Line to line and line to ground)
Drive Overload Trip Current overload value is exceeded.
Programmable to allow up to 150% of
drive current for one minute.
Instantaneous 215% of drive rated current
Overcurrent Trip
Phase Loss Trip DC bus ripple threshold exceeded
Overtemperature Trip Drive heatsink temperature exceeds 95°C (203ºF)
Short Circuit Trip Protects against output phase to phase fault
Ground Fault Trip Protects against output phase to ground fault
Motor Thermal Trip Electronically protects the motor from overheating
due to loading conditions
Approvals & Listings
UL, cUL UL File #E171230
IEC Meets IEC Vibration, Mechanical Shock and
Electromagnetic Immunity Standards
CE Designed for marking
NEMA NEMA 1 enclosure type
ISO 9002 Certified Manufacturing Facility
Dimensions
20
Commander SE
www.emersonct.com
Input / Output Bi-polar Analog Input Card SE51
Memory QuicKey Cloning Tool SE55
Communication RS485 / Modbus RTU Standard
Profibus-DP SE73
Interbus-S SE74
DeviceNet SE77DN
CANOpen SE77CO
PC to Drive Configuration Tool SESoft
Accessories RS232/485 Cable SE71
Operator Remote Keypad CTKP
Interface CT Operator Interface CTIU
Accessories Cable Shield Clamps SE11 to SE14
Extended 5-year Warranty SE1WE to SE5WE
Warranty
Commander SE
Options / Software / Accessories
Overview
This simple and easy drive also provides flexibility
with easy to install options. Drive set-up is quick and
convenient using our remote keypad or SESoft, our
Windows based configuration tool. The SE QuicKey
allows parameter cloning for fast parameter storage and
transfer, making it easy to add or replace drives within
your system. The Commander SE easily connects into
your network with a wide range of fieldbus protocols
and operator interface options.
At-A-Glance
Option Description Catalog Number
Commander SE
21
1-800-893-2321
RS485 / Modbus RTU Standard
Profibus-DP SE73
Interbus-S SE74
DeviceNet SE77DN
CANOpen SE77CO
PL1 1 Bi-polar Analog Input
(±10 VDC, 22k Ohms)
2 0V Common
PL2 1 0V Common
(Interface 2 0 to +10 VDC Analog Output
connections 3 +24 VDC Supply for option card
to Commander SE) 4 Digital Input (+24 VDC)
to control relay
5 Run Forward Output (+24 VDC)*
6 Run Reverse or Run Forward / Reverse
Output (+24 VDC)*
PL3 1 Relay Contact Common
(48 VAC / DC, 2A resistive)
2 Relay Contact (Normally Open)
Commander SE
Input / Output Modules
Bi-polar Analog Input Card (SE51)
The bi-polar speed reference input card (SE51) allows
the direction of a motor to be controlled via a speed
potentiometer or external bi-polar speed reference
rather than the forward/reverse terminal selector.
The +10V potentiometer reference can be supplied
from the drive (term. #3) or from an external power
supply. The –10V potentiometer reference must be
supplied from an external supply. The SE51 also has
a relay that is controlled by the digital output (default
“zero speed”) of the drive.
Communications
Communication Cards
(SE73, SE74, SE77DN, SE77CO)
Each fieldbus interface
for the Commander SE
is a single option card
that fits within the
drive. Parameter data is
transferred to and from
the Commander SE using
a 2-wire RS485 link into
the RJ45 serial communications port on the drive.
Memory
QuicKey / Cloning Module (SE55)
The QuicKey is a small, encapsulated
memory module that stores the entire
set of the drive’s parameter values. It
plugs onto the SE drive near the control
terminals. The Commander SE may be
programmed to download / upload a set of parameters
to / from the QuicKey or to operate with or without the
module installed. Once the information is stored in the
QuicKey, it may be removed from the drive for future
use such as cloning other drives or programming a
replacement drive.
SE51 Terminal Diagram
SE51 Terminal Description
* Directional control of Commander SE
Signal Connector Pin # Function
Communication Interface Card
Protocol* Catalog Number
* Maximum communication rate through RJ45 port is 19.2 kbaud.
Commander SE operates as slave node only.
22
Commander SE
www.emersonct.com
Commander SE
PC to Drive Accessories
Drive Configuration Tool (SESoft)
SESoft is a complimentary Windows based drive
configuration tool designed to enable the complete
control and display of all parameters within a
Commander SE. A set-up wizard guides the user in
entering motor and application data. Motor data may
be supplied from the motor nameplate, or the user
may select a motor from the database supplied in the
wizard. A monitoring screen displays real-time drive
values such as current, voltage and DC bus level. SESoft
communicates via the computer’s serial port and the
Commander SE’s RJ45 port using the CT Comms Cable.
For more information, refer to the Accessories
Section on page 138.
Programming / Configuration Cable
Using a special RS232 to RS485 converter you can connect
the PC to the RJ45 serial port on the front of the drive. A
special pre-made cable is available from Control Techniques
for this purpose – this same cable is used with other Control
Techniques – products that use a RJ45 RS485 connector such
as the Unidrive SP.
Catalog Number Description
CT Comms Cable PC-to-drive Comms Cable
Commander SE
23
1-800-893-2321
SE11 1
SE12 2
SE13 3
SE14 4
Commander SE
Operator Interfaces
Universal Keypad (CTKP)
The CTKP Universal Keypad
is an ideal maintenance tool for
use with CT’s digital drives (SE,
Unidrive, Mentor II, Quantum III)
and option modules (UD7X, MD
series). Five navigation keys and
plain text parameter descriptions
make the CTKP easy to use for viewing and modifying
drive data. The keypad is designed for hand–held or
panel mounting. The IP65 rating, screw-down terminals
and stress relief for cable connections assure a rugged
and robust design.
An RS485 cable with an RJ45 connector on the
Commander SE end and dressed wires on
the CTKP end is available (order Catalog Number
CTKP-SE-485-XXX). (XXX=ft.)
For more information, refer to the Accessories
Section on page 154.
Operator Interface Unit
(CTIU)
The CTIU operator interface units incorporate
a back-lit LCD display and easy-to-use navigation
keys. Using the “WYSIWIG” page editor, they can
be programmed to display a variety of menus,
submenus, alarms, fault conditions and other critical
information. The CTIUs support a range of capabilities
including multiple font sizes, real time trends and
graphs, scheduling and background programs. They
communicate via 2 or 4-wire RS485 and, to simplify
installation, CTIUs are rated NEMA 4/12 and require no
screw mounting holes.
An RS485 cable with an RJ45 connector on the
Commander SE end and dressed wires on
the CTIU end is available (order Catalog Number
CTIU-CTD-485-XXX). (XXX=ft.)
For more information, refer to the Accessories
Section on pages 152-153.
Accessories
Cable Shield Clamps
The cable shield
clamps are used with
the Commander SE
to stabilize wire / cable
connections when
mounting a drive inside
an enclosure. The
clamps attach to the
bottom of the Commander
SE drive and provide a convenient shielded ground
connection.
Warranty
Extended Warranty
An industry-leading two-year warranty is standard
for Commander SE drives. An extended warranty is
available that increases the warranty period to five years.
Clamp Commander SE
Catalog Number Size
1 SE1WE
2 SE2WE
3 SE3WE
4 SE4WE
5 SE5WE
Commander SE Size Catalog Number
CTIU Family