Did ≥10% of all
sprinkler heads/
nozzles tested fail?
15% ≤R
FB
≤ 20%?
Extended testing Case 1
(for failure rates between R
FB
≤ 20%)
Function test
1
2 randomly selected sprinklers per sprinkler
section. Sprinkler sections should be selected as follows:
- If number of sections <20, test all sections;
- If number of sections is between 20 and 40, test 20
sections;
- If number of sections >40, test 50% of the sections.
Extended testing Case 2
(for failure rates above 20%)
Function test
1
7 randomly selected sprinklers from
each sprinkler section. All sprinkler sections to be
tested except where the decision has been made to
replace all sprinklers at this stage.
Are there any
sections where both
sprinkler heads/
nozzleds tested
failed?
For the sections
where both
sprinkler heads/
nozzles tested
failed undertake
additional function
testing
1
of a
further 10 sprinkler
heads/nozzles per
affected section.
Are there any
sections where 2 or
more of the additional
sprinkler heads/nozzles
tested failed?
Part 2 - Extended testing
For any section with a type
failure rate greater than 10%
replace all sprinkler heads/
nozzles of this type.
No further action required, situation will be
monitored at next Annual Survey.
For any section with a type failure rate
greater than 15% replace all sprinkler
heads/nozzles of this type. Remaining
sections will be monitored at next Annual
Survey
Are there any sections
with a failure rate >15%?
If the number of sprinkler
heads/nozzles tested in any
particular section represents
less than 10% of all sprinkler
heads/nozzles installed in this
section a decision may be to
conduct further function testing
1
limited to 30% of the total
number of sprinkler heads/
nozzles in that section and the
results can be reassessed with
all sprinkler heads/nozzles
tested in that section being
considered.
After further testing are
there any sections with a
type failure rate >15%?
For each type that has
failed Basic testing obtain
the Failure rate, R
FB.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
AND
OR