https://edocs.imo.org/Final Documents/English/MSC.1-CIRC.1516 (E).docx
E
4 ALBERT EMBANKMENT
LONDON SE1 7SR
Telephone: +44 (0)20 7735 7611 Fax: +44 (0)20 7587 3210
MSC.1/Circ.1516
8 June 2015
AMENDMENTS TO THE REVISED GUIDELINES FOR THE MAINTENANCE
AND INSPECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES
(MSC.1/CIRC.1432)
1 The Maritime Safety Committee, at its ninety-fifth session (3 to 12 June 2015),
approved amendments to the Revised guidelines for the maintenance and inspection of fire
protection systems and appliances (MSC.1/Circ.1432), as set out in the annex, concerning
testing of automatic sprinkler systems, prepared by the Sub-Committee on Ship Systems and
Equipment, at its second session.
2 Member Governments are invited to use the amendments when applying
MSC.1/Circ.1432 and to bring the amendments to the attention of ship designers, shipyards,
shipowners, systems manufactures and all parties concerned.
***
MSC.1/Circ.1516
Annex, page 1
https://edocs.imo.org/Final Documents/English/MSC.1-CIRC.1516 (E).docx
ANNEX
AMENDMENTS TO THE REVISED GUIDELINES FOR THE MAINTENANCE
AND INSPECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES
(MSC.1/CIRC.1432)
1 Paragraph 3.4 is amended to read as follows:
"3.4 In addition to the onboard maintenance and inspections stated in these
guidelines, manufacturer's maintenance and inspection guidelines should be
followed. The quality of water in automatic sprinkler systems is of particular
importance and should be maintained in accordance with manufacturer guidelines.
Records of water quality should be maintained on board in accordance with
the manufacturer's guidelines."
2 A new paragraph 6.5 is added after the existing paragraph 6.4, as follows:
"6.5 Water mist, water spray and sprinkler systems
Assess system water quality in the header tank and pump unit against the
manufacturer's water quality guidelines."
3 Paragraph 7.5 is amended to read as follows:
"7.5 Water mist, water spray and sprinkler systems
.1 verify proper operation of all water mist, water-spray and sprinkler
systems using the test valves for each section;
.2 visually inspect all accessible components for proper condition;
.3 externally examine all high pressure cylinders for evidence of
damage or corrosion;
.4 check the hydrostatic test date of all high pressure cylinders;
.5 functionally test all fixed system audible and visual alarms;
.6 flow test all pumps for proper pressure and capacity;
.7 test all antifreeze systems for adequate freeze protection;
.8 test all system cross connections to other sources of water supply
for proper operation;
.9 verify all pump relief valves, if provided, are properly set;
.10 examine all filters/strainers to verify they are free of debris and
contamination;
.11 verify all control/section valves are in the correct position;
MSC.1/Circ.1516
Annex, page 2
https://edocs.imo.org/Final Documents/English/MSC.1-CIRC.1516 (E).docx
.12 blow dry compressed air or nitrogen through the discharge piping
of dry pipe systems, or otherwise confirm the pipework and
nozzles are clear of any obstructions. This may require the
removal of nozzles, if applicable;
.13 test emergency power supply switchover, where applicable;
.14 visually inspect all sprinklers focusing in areas where sprinklers
are subject to aggressive atmosphere (like saunas, spas, kitchen
areas) and subject to physical damage (like luggage handling
areas, gyms, play rooms, etc.) so that all sprinklers are inspected
within one year. Sprinklers with obvious external damage,
including paint, should be replaced and not included in the number
of sprinklers tested in subparagraph .17;
.15 check for any changes that may affect the system such as
obstructions by ventilation ducts, pipes, etc.;
.16 test a minimum of one section in each open head water mist
system by flowing water through the nozzles. The sections tested
should be chosen so that all sections are tested within a five-year
period;
.17 test automatic sprinklers and automatic water mist nozzles in
accordance with the following flow chart:
MSC.1/Circ.1516
Annex, page 3
https://edocs.imo.org/Final Documents/English/MSC.1-CIRC.1516 (E).docx
Has the Automatic Sprinkler
System been installed on the
ship for 5 years or more?
Functional test
1
of
2 randomly
selected sprinkler
heads/nozzles of
each type
2
installed on board.
Did one or
more sprinkler
heads/nozzles
fail?
For each type
2
of
sprinkler head/
nozzle installed on
board functional
test
1
of 2 randomly
selected sprinklers
heads/nozzles per
section in 10
sections (20
sprinkler heads/
nozzles in total).
For each type tested did
3 or more out of 20 sprinkler
heads/nozzles fail? (i.e. failure
rate, R
FB
15%)
No further action required, situation will be monitored at next Annual Survey.
Are there any
sections where both
sprinkler heads/
nozzles tested
failed?
For the sections
where both
sprinkler heads/
nozzles tested
failed undertake
additional testing
of a further 10
sprinkler heads/
nozzles per
affected section.
Part 1 - Basic Testing
Are there any sections
where 2 or more of the
additional sprinkler heads/
nozzles tested failed?
Replace all sprinkler
heads/nozzles in Sections
which failed and
commission as necessary.
Yes
Yes
Yes
Yes
No
No
No
No
Yes
No
For each type that failed
proceed to Extended
testing in Part 2.
Extended testing of these
sections is not required.
Start
AND
MSC.1/Circ.1516
Annex, page 4
https://edocs.imo.org/Final Documents/English/MSC.1-CIRC.1516 (E).docx
Did 10% of all
sprinkler heads/
nozzles tested fail?
15% R
FB
20%?
Extended testing Case 1
(for failure rates between R
FB
20%)
Function test
1
2 randomly selected sprinklers per sprinkler
section. Sprinkler sections should be selected as follows:
- If number of sections <20, test all sections;
- If number of sections is between 20 and 40, test 20
sections;
- If number of sections >40, test 50% of the sections.
Extended testing Case 2
(for failure rates above 20%)
Function test
1
7 randomly selected sprinklers from
each sprinkler section. All sprinkler sections to be
tested except where the decision has been made to
replace all sprinklers at this stage.
Are there any
sections where both
sprinkler heads/
nozzleds tested
failed?
For the sections
where both
sprinkler heads/
nozzles tested
failed undertake
additional function
testing
1
of a
further 10 sprinkler
heads/nozzles per
affected section.
Are there any
sections where 2 or
more of the additional
sprinkler heads/nozzles
tested failed?
Part 2 - Extended testing
For any section with a type
failure rate greater than 10%
replace all sprinkler heads/
nozzles of this type.
No further action required, situation will be
monitored at next Annual Survey.
For any section with a type failure rate
greater than 15% replace all sprinkler
heads/nozzles of this type. Remaining
sections will be monitored at next Annual
Survey
Are there any sections
with a failure rate >15%?
If the number of sprinkler
heads/nozzles tested in any
particular section represents
less than 10% of all sprinkler
heads/nozzles installed in this
section a decision may be to
conduct further function testing
1
limited to 30% of the total
number of sprinkler heads/
nozzles in that section and the
results can be reassessed with
all sprinkler heads/nozzles
tested in that section being
considered.
After further testing are
there any sections with a
type failure rate >15%?
For each type that has
failed Basic testing obtain
the Failure rate, R
FB.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
AND
OR
MSC.1/Circ.1516
Annex, page 5
https://edocs.imo.org/Final Documents/English/MSC.1-CIRC.1516 (E).docx
Explanatory notes to the flow chart
1 Functional test is defined as a test that demonstrates
the operation and flow of water from sprinkler head/nozzle.
2 Type is defined as each different manufacturer model of
sprinkler head/nozzle.
3 Static/standby pressure is defined as the constant pressure
maintained in the system at all times prior to activation.
4 All testing should be carried out at static/standby pressure.
5 Failure rate (R
FB
) is the number of sprinkler heads/nozzles
to fail testing divided by test sample size multiplied
by 100; and
.18 during basic testing, and extended testing when applicable, of
automatic sprinkler heads/nozzles as outlined in subparagraph .17,
water quality testing should be conducted in each corresponding
piping section. Note should a tested sprinkler fail, assessing
the corresponding water quality at that time would assist in
determining the cause of failure."
4 Paragraph 9.3 is replaced by the following:
"9.3 Water mist, water spray and sprinkler systems
.1 flush all ro-ro deck deluge system piping with water, drain and
purge with air;
.2 perform internal inspection of all control/section valves; water
quality testing should be conducted in all corresponding piping
sections, if not previously tested as outlined in paragraph 7.5.18
within the last five years;
.3 check condition of any batteries, or renew in accordance with
manufacturer's recommendations; and
.4 for each section where the water is refilled after being drained or
flushed, water quality should meet manufacturer's guidelines.
Testing of the renewed water quality should be conducted and
recorded as a new baseline reference to assist future water quality
monitoring for each corresponding section."
___________